Parameter
Name
Motor noise suppression and measures against EMC and leakage current — Reducing
mechanic resonance
(speed smoothing control) (Pr.653, Pr.654)
Speed smoothing
653
control
Speed smoothing
654
cutoff frequency
665
Refer to Pr.52.
779
Refer to Pr.331.
791, 792
Refer to Pr.7 and Pr.8.
Function assignment of external terminal and control — Pulse train output of output
power (Y79 signal) (Pr.799)
Pulse increment
799
setting for output
power
IPM motor control — Control method selection (Pr.800)
Control method
800
selection
IPM motor control — Proportional gain setting for speed loops (Pr.820, Pr.821)
Speed control P gain
820
1
Speed control integral
821
time 1
867
Refer to Pr.54 to Pr.56.
870
Refer to Pr.43.
872
Refer to Pr.251.
Incre-
Initial
Range
ments
Value
0 to 200%
0.1%
0
0.01Hz
20Hz
0 to 120Hz
0.1kWh,
1kWh,
0.1kWh
1kWh
10kWh,
100kWh,
1000kWh
9
1
20
20
1%
25%
0 to 1000%
0.001s
0.333s
0 to 20s
Description
The torque fluctuation is reduced to reduce
vibration due to mechanical resonance.
Set the minimum value for the torque
variation cycle (frequency).
Pulse train output of output power (Y79) is
output in pulses at every output current
(kWh) that is specified.
IPM motor test operation (Motor is not
driven even if it is connected.)
Normal operation (Motor can be driven.)
The proportional gain during speed control
is set. (Setting this parameter higher
improves the trackability for speed
command changes. It also reduces the
speed fluctuation due to a load fluctuation.)
The integral time during speed control is set.
(Setting this parameter lower shortens the
return time to the original speed when the
speed fluctuates due to external forces. )
Parameter list
: enabled
× : disabled
V/F
V/F
V/F
S
S
S
MFVC
MFVC
MFVC
IPM
IPM
IPM
IPM
IPM
IPM
5