Parameter list
Parameter
Name
Setting of the parameter unit and operation panel — Operation selection of the operation
panel (Pr.161)
Frequency setting/key
161
lock operation
selection
162 to 165
Refer to Pr.57 and Pr.58.
166, 167
Refer to Pr.150 to Pr.153.
168, 169
Parameter for manufacturer setting. Do not set.
170, 171
Refer to Pr.52.
172 to 174
Refer to Pr.160.
Function assignment of external terminal and control — Function assignment of input
terminals (Pr.178 to Pr.189)
STF terminal function
178
selection
STR terminal function
179
selection
RL terminal function
180
selection
RM terminal function
181
selection
RH terminal function
182
selection
RT terminal function
183
selection
AU terminal function
184
selection
JOG terminal function
185
selection
CS terminal function
186
selection
MRS terminal
187
function selection
STOP terminal
188
function selection
RES terminal function
189
selection
104
Incre-
Initial
Range
ments
Value
0
1
1
0
10
11
0 to 8,
10 to 12, 14,
1
60
16, 24, 25, 60,
62, 64 to 67,
70 to 72, 9999
0 to 8,
10 to 12, 14,
1
61
16, 24, 25, 61,
62, 64 to 67,
70 to 72, 9999
1
0
0 to 8,
1
1
10 to 12, 14,
16, 24, 25, 62,
64 to 67,
1
2
70 to 72, 9999
1
3
0 to 8,
10 to 12, 14,
1
4
16, 24, 25,
62 to 67,
70 to 72, 9999
1
5
1
6
0 to 8,
10 to 12, 14,
1
24
16, 24, 25, 62,
64 to 67,
70 to 72, 9999
1
25
1
62
Description
Setting dial frequency
setting
Key lock invalid
Setting dial
potentiometer
Setting dial frequency
setting
Key lock valid
Setting dial
potentiometer
0: Low-speed operation command (RL)
1: Middle-speed operation command (RM)
2: High-speed operation command (RH)
3: Second function selection (RT)
4: Terminal 4 input selection (AU)
5: Jog operation selection (JOG)
6: Selection of automatic restart after
instantaneous power failure, flying start
(CS)
7: External thermal relay input (OH)
8: 15-speed selection (combination with three
speeds RL, RM, RH) (REX)
10: Inverter run enable signal (FR-HC, MT-HC,
FR-CV connection) (X10)
11: FR-HC, MT-HC connection, instantaneous
power failure detection (X11)
12: PU operation external interlock (X12)
14: PID control valid terminal(X14)
16: PU/External operation switchover (X16)
24: Output stop (MRS)
25: Start self-holding selection (STOP)
60: Forward rotation command (STF)
(assigned to STF terminal (Pr.178) only)
61: Reverse rotation command (STR)
(assigned to STR terminal (Pr.179) only)
62: Inverter reset (RES)
63: PTC thermistor input (PTC) (assigned to
AU terminal (Pr.184) only)
64: PID forward/reverse action switchover
(X64)
65: PU/NET operation switchover (X65)
66: External/NET operation switchover (X66)
67: Command source switchover (X67)
70: DC feeding operation permission (X70)
71: DC feeding cancel (X71)
72: PID integral value reset (X72)
9999: No function
: enabled
× : disabled
×
×
×
×
×
×
×
×
×
×
×
×
×