2.4.3

Specification of main circuit terminal

Terminal
Terminal Name
Symbol
R/L1,
S/L2,
AC power input
T/L3
U, V, W
Inverter output
R1/L11,
Power supply for
S1/L21
control circuit
Brake unit
P/+, N/-
connection
DC reactor
P/+, P1
connection
PR, PX
Please do not remove or use terminals PR and PX or the jumper connected.
Earth (ground)
2.4.4
Terminal arrangement of the main circuit terminal, power supply and the motor
wiring
200V class
FR-F720P-0.75K, 1.5K
Screw size (M4)
R/L1 S/L2 T/L3
Jumper
R1/L11 S1/L21
N/-
M
Power supply
Motor
As this is an inside cover fixing screw,
do not remove it.
Connect to the commercial power supply.
Keep these terminals open when using the high power
factor converter (FR-HC, MT-HC) or power regeneration
common converter (FR-CV).
Connect a three-phase squirrel-cage motor or dedicated
IPM motor.
Connected to the AC power supply terminals R/L1 and S/
L2. To retain the fault display and fault output or when
using the high power factor converter (FR-HC, MT-HC) or
power regeneration common converter (FR-CV), remove
the jumpers from terminals R/L1 and R1/L11, and S/L2
and S1/L21, and apply external power to these terminals.
The power capacity necessary when separate power is
supplied from R1/L11 and S1/L21 differs according to the
inverter capacity.
15K or lower
200V class
400V class
Connect the brake unit (FR-BU2, FR-BU, BU and MT-
BU5), power regeneration common converter (FR-CV),
high power factor converter (FR-HC and MT-HC) or power
regeneration converter (MT-RC).
For the 55K or lower, remove the jumper across terminals
P/+ and P1, and connect the DC reactor. (Be sure to
connect the DC reactor supplied with the 75K or higher.)
When a DC reactor is not connected, the jumper across
terminals P/+ and P1 should not be removed.
For earthing (grounding) the inverter chassis. Must be
earthed (grounded).
Jumper
PR
P/+
PX
Screw size
(M4)
Charge lamp
Description
18.5K
60VA
80VA
60VA
60VA
FR-F720P-2.2K to 5.5K
Screw size (M4)
R/L1 S/L2 T/L3
Jumper
R1/L11 S1/L21
M
Power
Motor
supply
Wiring
Refer to
Page
11
11
18
22K or higher
80VA
80VA
28
36
17
Jumper
PR
N/-
P/+
PX
Screw size
Charge lamp
(M4)
2
11