Parameter
Name
Function assignment of external terminal and control — Function assignment of output
terminals (Pr.190 to Pr.196)
RUN terminal function
190
selection
SU terminal function
191
selection
IPF terminal function
192
selection
OL terminal function
193
selection
FU terminal function
194
selection
ABC1 terminal
195
function selection
ABC2 terminal
196
function selection
232 to 239
Refer to Pr.4 to Pr.6.
240
Refer to Pr.72.
241
Refer to Pr.125 and Pr.126.
242, 243
Refer to Pr.73.
Incre-
Initial
Range
ments
Value
1
0
0 to 5, 7, 8,
1
1
10 to 19, 25,
26, 45 to 48,
57, 64, 67,
70, 79, 85,
90 to 96, 98,
99,
100 to 105,
1
2
107, 108,
110 to 116,
125, 126,
145 to 148,
157, 164, 167,
170, 179, 185,
190 to 196,
198, 199,
1
3
9999
1
4
0 to 5, 7, 8,
10 to 19,
25, 26,
45 to 48, 57,
1
99
64, 67, 70, 79,
85, 90, 91,
94 to 96,
98, 99,
100 to 105,
107, 108,
110 to 116,
125, 126,
145 to 148,
1
9999
157, 164, 167,
170, 179, 185,
190, 191,
194 to 196,
198, 199, 9999
Description
0, 100: Inverter running (RUN)
1, 101: Up to frequency (SU)
2, 102: Instantaneous power failure/
undervoltage (IPF)
3, 103: Overload warning (OL)
4, 104: Output frequency detection (FU)
5, 105: Second output frequency detection
(FU2)
7, 107: Regenerative brake pre-alarm (RBP)
(Only for the 75K or higher)
8, 108: Electronic thermal relay function
prealarm (THP)
10, 110: PU operation mode (PU)
11, 111: Inverter operation ready (RY)
12, 112: Output current detection (Y12)
13, 113: Zero current detection (Y13)
14, 114: PID lower limit (FDN)
15, 115: PID upper limit (FUP)
16, 116: PID forward/reverse rotation output
(RL)
17, —: Electronic bypass MC1 (MC1) *
18, —: Electronic bypass MC2 (MC2) *
19, —: Electronic bypass MC3 (MC3) *
25, 125: Fan fault output (FAN)
26, 126: Heatsink overheat pre-alarm (FIN)
45, 145: Inverter running and start command is
ON(RUN3)
46, 146: During deceleration at occurrence of
power failure (retained until release)
(Y46)
47, 147: During PID control activated (PID)
48, 148: PID deviation limit (Y48)
57, 157: IPM motor control (IPM)
64, 164: During retry (Y64)
67, 167: During power failure (Y67)
70, 170: PID output interruption (SLEEP)
79, 179: Pulse train output of output power
(Y79)
85, 185: DC current feeding (Y85)
90, 190: Life alarm (Y90)
91, 191: Fault output 3 (power-OFF signal)
(Y91)
92, 192: Energy saving average value updated
timing (Y92)
93, 193: Current average monitor signal (Y93)
94, 194: Fault output 2 (ALM2)
95, 195: Maintenance timer signal (Y95)
96, 196: Remote output (REM)
98, 198: Alarm output (LF)
99, 199: Fault output (ALM)
9999: No function
0 to 99: Positive logic, 100 to 199: Negative
logic
* Available under V/F control and Simple
magnetic flux vector control
Parameter list
: enabled
× : disabled
×
×
×
×
×
×