Parameter
Name
Useful functions — To display life of inverter parts (Pr.255 to Pr.259)
Life alarm status
255
display
Inrush current limit
256
circuit life display
Control circuit
257
capacitor life display
Main circuit capacitor
258
life display
Main circuit capacitor
259
life measuring
260
Refer to Pr.72.
Motor brake and stop operation — Decelerate the motor to a stop at instantaneous
power failure (Pr.261 to Pr.266)
Operation selection at power failure and instantaneous power failure — Decelerate the
motor to a stop at instantaneous power failure (Pr.261 to Pr.266)
Power failure stop
261
selection
Subtracted frequency
262
at deceleration start
Subtraction starting
263
frequency
Power-failure
264
deceleration time 1
Power-failure
265
deceleration time 2
Incre-
Initial
Range
ments
Value
1
0
(0 to 15)
1%
100%
(0 to 100%)
1%
100%
(0 to 100%)
1%
100%
(0 to 100%)
1
0
0, 1
0
1
1
0
2
21
22
0.01Hz
3Hz
0 to 20Hz
0 to 400Hz
0.01Hz
60Hz *
9999
0.1/
0 to 3600/
5s
0.01s
360s
0 to 3600/
0.1/
360s
9999
0.01s
9999
Description
Displays whether the control circuit capacitor, main
circuit capacitor, cooling fan, and each parts of the
inrush current limit circuit has reached the life alarm
output level or not.
Displays the deterioration degree of the inrush
current limit circuit. Reading only
Displays the deterioration degree of the control
circuit capacitor. Reading only
Displays the deterioration degree of the main
circuit capacitor. Reading only
The value measured by Pr. 259 is displayed.
Start measuring the main circuit capacitor life.
Switch the power supply ON again and check
the Pr. 259 setting. Measurement is complete if
the setting is "3". Set the deterioration degree
in Pr.258.
Operation at
At power restoration
undervoltage
during power failure
or power
deceleration
failure
Coasts to a stop Coasts to a stop
Decelerates
Decelerates to a stop
to a stop
Decelerates
Accelerates again
to a stop
Decelerates
Decelerates to a stop
to a stop
Decelerates
Accelerates again
to a stop
Normally operation can be performed with the
initial value unchanged. But adjust the frequency
according to the magnitude of the load
specifications (moment of inertia, torque).
When output frequency ≥ Pr.263
Decelerate from the speed obtained from
(output frequency - Pr.262).
When output frequency < Pr.263
Decelerate from output frequency
Decelerate from the speed obtained from
(output frequency - Pr.262).
Set a deceleration slope down to the frequency
set in Pr.266.
Set a deceleration slope below the frequency
set in Pr.266.
Same slope as in Pr.264
Parameter list
: enabled
× : disabled
×
×
×
×
×
×
×
×
×
×
×
×
Deceleration
time to a stop
-
Depends on
Pr. 262 to Pr.
266 settings
Depends on
Pr. 262 to Pr.
266 settings
Automatically
adjusts the
deceleration
time
Automatically
adjusts the
deceleration
time
107
5