Mitsubishi Electric FR-F720P-0.75K Instruction Manual Page 100

Fr-f700p series.
Hide thumbs

Advertisement

Parameter
Name
Monitor display and monitor output signal — Changing DU/PU monitored items and
clearing cumulative monitors (Pr.52, Pr.170, Pr.171, Pr.268, Pr.563, Pr.564, Pr.891)
DU/PU main display
52
data selection
Watt-hour meter clear
170
Operation hour meter
171
clear
Monitor decimal digits
268
selection
Energization time
563
carrying-over times
Operating time
564
carrying-over times
Cumulative power
monitor digit shifted
891
times
Monitor display and monitor output signal — Changing the monitored item to be output
from terminal FM/AM
(Pr.54 to Pr.56, Pr.158, Pr.867)
FM terminal function
54
selection
Frequency monitoring
55
reference
Current monitoring
56
reference
AM terminal function
158
selection
AM output filter
867
*1
The setting depends on the inverter capacity (55K or lower/75K or higher)
*2
Performing IPM parameter initialization changes the settings.
Incre-
Initial
Range
ments
Value
0, 5, 6, 8 to 14,
17, 20, 23 to
1
0
25, 50 to 57,
100
0
10
1
9999
9999
1
9999
0, 9999
0
1
9999
1
9999
1
0
(0 to 65535)
1
0
(0 to 65535)
0 to 4
1
9999
9999
1 to 3, 5, 6,
1
1
8 to 14, 17, 21,
24, 50, 52, 53
0.01Hz
60Hz
0 to 400Hz
*2
Rated
0.01/
0 to 500/
inverter
0.1A
0 to 3600A
*1
*1
current
*2
1 to 3, 5, 6,
1
1
8 to 14, 17, 21,
24, 50, 52, 53
0.01s
0.01s
0 to 5s
(Refer to page 43)
Description
Select the monitor to be displayed on the
operation panel and parameter unit.
The setting value of "9" is available only for the
75K or higher.
Set "0" to clear the watt-hour meter monitor.
Set the maximum value when monitoring from
communication to 0 to 9999kWh.
Set the maximum value when monitoring from
communication to 0 to 65535kWh.
Set "0" to clear the operation time monitor.
Setting "9999" has no effect.
Displays the monitor as integral value.
Displays the monitor in increments of 0.1.
No fixed decimal position
The numbers of cumulative energization time
monitor exceeded 65535h is displayed.
Reading only
The numbers of operation time monitor
exceeded 65535h is displayed.
Reading only
Set the number of times to shift the cumulative
power monitor digit.
Clamps the monitor value at maximum.
No shift
Clears the monitor value when it exceeds the
maximum value.
Select the monitor output to terminal FM.
The setting value of "9" is available only for the
or higher.
75K
Set the full-scale value to output the output
frequency monitor value to terminal FM and
AM.
Set the full-scale value to output the output current
monitor value to terminal FM and AM.
Select the monitor output to terminal AM.
The setting value of "9" is available only for the
75K or higher.
Set the output filter of terminal AM.
Parameter list
: enabled
× : disabled
×
×
×
×
×
×
×
×
×
×