Causes and corrective actions
Operation Panel
Indication
Name
Description
Check point
Corrective action
Operation Panel
Indication
Name
Description
Check Point
Corrective Action
Operation Panel
Indication
Name
Description
Corrective action
CAUTION
• If protective functions of E.ILF, E.SOT, E.PTC, E.PE2, E.CDO, E.IOH, E.SER, E.AIE, E.PID are activated when using the FR-
PU04, "Fault 14" appears.
Also when the faults history is checked on the FR-PU04, the display is "E.14".
• If faults other than the above appear, contact your sales representative.
130
E.AIE
Analog input fault
Stops the inverter output when a 30mA or higher current or a 7.5V or higher voltage is input to terminal
2 while the current input is selected by Pr.73 Analog input selection, or to terminal 4 while the current
input is selected by Pr.267 Terminal 4 input selection.
Check the setting of Pr. 73 Analog input selection and Pr. 267 Terminal 4 input selection. (
Chapter 4 of the Instruction Manual (Applied).)
Either give a frequency command by current input or set Pr. 73 Analog input selection or Pr. 267 Terminal
4 input selection to voltage input.
E.PID
PID signal fault
If any of PID upper limit (FUP), PID lower limit (FDN), and PID deviation limit (Y48) turns ON during PID
control, inverter shuts off the output. This function is active under the following parameter settings: Pr.554 PID
signal operation selection ≠ "0,10", Pr.131 PID upper limit ≠ "9999", Pr.132 PID lower limit ≠ "9999", and Pr.553 PID
deviation limit ≠ "9999". This protective function is not active in the initial setting (Pr.554 = "0", Pr.131 = "9999",
Pr.132 = "9999", Pr.553 = "9999").
· Check if the measured PID value is greater than the upper limit (Pr.131) or smaller than the lower limit
(Pr.132).
· Check if the absolute PID deviation value is greater than the limit value (Pr.553).
Make correct settings for Pr.131 PID upper limit, Pr.132 PID lower limit, Pr.553 PID deviation limit.
Chapter 4 of the Instruction Manual (Applied))
E.13
Internal circuit fault
Trips when an internal circuit error occurred.
Please contact your sales representative.
FR-PU04
Fault 14
FR-PU07
Analog in error
FR-PU04
Fault 14
Fault
FR-PU07
PID Signal Error
FR-PU04
Fault 13
FR-PU07
Refer to
(
Refer to