Parameter
Name
Communication operation and setting — Initial setting of RS-485 communication
(Pr.117 to Pr.124, Pr.551)
Communication operation and setting — Control of parameter write by communication
(Pr.342)
PU communication
117
station number
PU communication
118
speed
PU communication
119
stop bit length
PU communication
120
parity check
Number of PU
121
communication retries
PU communication
122
check time interval
PU communication
123
waiting time setting
PU communication
124
CR/LF selection
Communication
EEPROM write
342
selection
PU mode operation
command source
551
selection
Incre-
Initial
Range
ments
Value
1
0
0 to 31
48, 96, 192,
1
192
384
0
1
1
1
10
11
0
1
2
1
2
0 to 10
1
1
9999
0
0.1s
9999
0.1 to 999.8s
9999
0 to 150ms
1
9999
9999
0
1
1
1
2
0
1
0
1
1
1
2
2
Description
Specify the inverter station number.
Set the inverter station numbers when two or
more inverters are connected to one personal
computer.
Set the communication speed.
The setting value × 100 equals the
communication speed.
For example, the communication speed is
19200bps when the setting value is "192".
Stop bit length
data length
1bit
8bit
2bit
8bit
1bit
7bit
2bit
7bit
Without parity check
With odd parity check
With even parity check
Set the permissible number of retries at
occurrence of a data receive error.
If the number of consecutive errors exceeds
the permissible value, the inverter trips.
If a communication error occurs, the inverter
will not come to trip.
No PU connector communication
Set the communication check time interval.
If a no-communication state persists for longer
than the permissible time, the inverter trips.
No communication check
Set the waiting time between data transmission
to the inverter and response.
Set with communication data.
Without CR/LF
With CR
With CR/LF
Parameter values written by communication are
written to the EEPROM and RAM.
Parameter values written by communication
are written to the RAM.
Select the RS-485 terminals as the PU
operation mode control source.
Select the PU connector as the PU operation
mode control source.
Parameter list
: enabled
× : disabled
5
99