 Enabled during Operation
When the Jogging Stop Selection (A039) is set to 03, 04, or 05, jogging operation will occur even if
the FW signal turns ON first.
However, if the JG signal turns OFF first, the motor will make a free-run stop.
5-9-7

2-step Acceleration/Deceleration (2CH)

• Use this function to change the acceleration/deceleration time on the way during
acceleration/deceleration.
• Allocate one of the Multi-function Input S1 to S8 Selection (C001 to C008) to 09 (2CH).
• For the 2-step acceleration/deceleration function, refer to 5-6 Acceleration/Deceleration Time
Settings on page 5-35.
Parameter
No.
C001 to
Multi-function Input S1 to S8
C008
Selection
5-9-8

Reset (RS)

• This function resets an inverter trip error.
• Allocate one of the Multi-function Input S1 to S8 Selection (C001 to C008) to 18 (RS).
• For the reset function, refer to 5-8 Reset Method Settings on page 5-47.
Parameter
No.
C001 to
Multi-function Input S1 to S8
C008
Selection
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
JG
Deceleration
FW
Normal
Jogging
operation
operation
Output
frequency
Free running
Accelerates according to the b088 setting
Function name
09: 2CH (2-step
Function name
18: RS (Reset)
Data
acceleration/deceleration)
Data
5 Basic Settings
Default data
Unit
Default data
Unit
5 - 57