Parameter
No.
b101
Free V/f Voltage 1 (V1)
b103
Free V/f Voltage 2 (V2)
b105
Free V/f Voltage 3 (V3)
b107
Free V/f Voltage 4 (V4)
b109
Free V/f Voltage 5 (V5)
b111
Free V/f Voltage 6 (V6)
b113
Free V/f Voltage 7 (V7)
Related functions
(Example) Output voltage [V]
Precautions for Correct Use
Precautions for Correct Use
Even if the Free V/f Voltage 1 to 7 are set to 800 V, the inverter cannot produce output voltage
higher than the input voltage or the value of the Motor Rated Voltage Selection (A082).
Be sure to check that the output characteristic setting is proper. An improper setting causes
overcurrent during acceleration or deceleration, or vibration of the motor and/or machine.
Output voltage [V]
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Function name
0. to 800.0
A044, A244, A344
V7
V6
V5
V4
V1
V2, V3
0
f1
f2
f3
V7
V6
0
f6
Data
Set the voltage at
each break point.
Output frequency [Hz]
f4
f5
f6
f7
The output voltage will be limited to
the applicable voltage even if
exceeded.
f7
Output frequency [Hz]
5 Basic Settings
Default
Description