2-Step Acceleration/Deceleration (2Ch); Reset (Rs) - Omron MX2 Series User Manual

Mx2 series type v1 multi-function compact inverter
Hide thumbs Also See for MX2 Series:
Table of Contents

Advertisement

Enabled during operation
When the Jogging Stop Selection (A039) is set to 03, 04, or 05, jogging operation is performed even
if the FW signal turns ON first.
However, if the JG signal turns OFF first, the motor falls in a free-run stop state.
JG
FW
Output
frequency
5-9-7

2-step Acceleration/Deceleration (2CH)

• Use this function to switch between two acceleration/deceleration time settings or change the accel-
eration/deceleration time on the way during acceleration/deceleration.
• Allocate one of the Multi-function Input S1 to S7 Selection (C001 to C007) to 09 (2CH).
• For the 2-step acceleration/deceleration function, refer to 5-6-3 2-step Acceleration/Deceleration
Function on page 5-37.
Parameter
No.
Multi-function Input S1 to S7
C001 to
C007
Selection
5-9-8

Reset (RS)

• This function resets an inverter trip error.
• Allocate one of the Multi-function Input S1 to S7 Selection (C001 to C007) to 18 (RS).
• For the reset function, refer to 5-8 Reset Method Settings on page 5-43.
Parameter
No.
Multi-function Input S1 to S7
C001 to
C007
Selection
Multi-function Compact Inverter 3G3MX2-V1 User's Manual (I585-E1)
During
Normal
Jogging operation
operation
Free-run
Accelerates according to b088 setting
Function name
09: 2CH (2-step acceleration/deceleration)
Function name
18: RS (Reset)
5 Basic Settings
Data
Default data
Data
Default data
5
Unit
Unit
5 - 53