Advertisement

5 Basic Settings
⚫ Enabled during operation
When the Jogging Stop Selection (A039) is set to 03, 04, or 05, jogging operation is performed even
if the FW signal turns ON first.
However, if the JG signal turns OFF first, the motor falls in a free-run stop state.
5-9-7

2-step Acceleration/Deceleration (2CH)

• Use this function to switch between two acceleration/deceleration time settings or change the accel-
eration/deceleration time on the way during acceleration/deceleration.
• Allocate one of the Multi-function Input 1 to 7 Selection (C001 to C007) to 09 (2CH).
• For the 2-step acceleration/deceleration function, refer to 5-6-3 2-step Acceleration/Deceleration
Function on page 5-36.
Parameter
No.
Multi-function Input 1 to 7
C001 to
C007
Selection
5-9-8

Reset (RS)

• This function resets an inverter trip error.
• Allocate one of the Multi-function Input 1 to 7 Selection (C001 to C007) to 18 (RS).
• For the reset function, refer to 5-8 Reset Method Settings on page 5-42.
Parameter
No.
Multi-function Input 1 to 7
C001 to
C007
Selection
5 - 52
Function name
09: 2CH (2-step acceleration/deceleration)
Function name
18: RS (Reset)
Multi-function Compact Inverter 3G3MX2-EV2 User's Manual (I666-E1)
Data
Default data
Data
Default data
Unit
Unit