7 Detailed Functions
Fault Monitor 1 to 6 [d081 to 086]
Use these functions to display the fault history of up to the last six faults.
To display the latest fault history, set the Fault Monitor 1 (d081).
<Displayed Items>
(a) Error code (Fault factor) (Displayed in E01 to E79.)*
(b) Output frequency at the trip [Hz]
(c) Output current at the trip [A]
(d) DC voltage between P and N on main circuit at the trip [V]
(e) Total RUN time of inverter before the trip [h]
(f) Total power ON time of inverter before the trip [h]
Note Refer to 10-1-2 Alarm Code List on page 10-3.
<Trip Monitor Display Sequence>
* Displays
if there is no trip.
Warning Monitor [d090]
Use this function to display a warning code if any inconsistency is found among the set data.
The program LED "PRG" remains lit during the warning, until the inconsistent data is corrected.
For details on the warning display, refer to 10-2 Warning Function on page 10-12.
7 - 12
*
(a) Trip factor
(b) Output
frequency
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
(d) P-N DC
(c) Output
voltage
current
(e) Total RUN
(f) Total power
tim
ON time