5-6-4

2-step Acceleration/Deceleration Function

• Use this function to switch between two acceleration/deceleration time settings or change the
acceleration/deceleration time on the way during acceleration/deceleration.
• The acceleration/deceleration time switching method can be selected from the following three.
• Switching via a multi-function input
• Automatic switching at a specified frequency
• Automatic switching via forward/reverse switching
Note that, automatic switching to 2-step acceleration/deceleration is disabled when the 3rd control
function is selected.
• To switch via a multi-function input terminal, set one of C001 to C008 to 09 (2CH).
Parameter
No.
A092
1st Acceleration Time 2
A292
2nd Acceleration Time 2
A392
3rd Acceleration Time 2
A093
1st Deceleration Time 2
A293
2nd Deceleration Time 2
A393
3rd Deceleration Time 2
1st 2-step
A094
Acceleration/Deceleration
Selection
2nd 2-step
Acceleration/Deceleration
A294
Selection
A095
1st 2-step Acceleration Frequency
A295
2nd 2-step Acceleration Frequency
A096
1st 2-step Deceleration Frequency
A296
2nd 2-step Deceleration Frequency
Related functions
*1 To enable the switching to the 2nd Acceleration Time 1/3rd Acceleration Time 1 and to the 2nd Deceleration
Time 1/3rd Deceleration Time 1, allocate one of the Multi-function Input S1 to S8 Selection (C001 to C008) to
08 (SET) or 17 (SET3) and turn ON that terminal.
*2 The default data was changed from the previous model.
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Function name
0.01 to 99.99
*1
100.0 to 999.9
1000. to 3600.
* 1
0.01 to 99.99
*1
100.0 to 999.9
1000. to 3600.
*1
00: Switched via 2CH terminal
01: Switched via setting (Example 2)
02: Switched only during
*1
0.00 to 99.99
*1
100.0 to 400.0
0.00 to 99.99
*1
100.0 to 400.0
F002, F202, F302, F003, F203, F303, C001 to C008
Data
(multi-function input set to 09)
(Example 1)
forward/reverse switching
(Example 3)
5 Basic Settings
Default
Unit
data
*2
s
10.00
*2
s
10.00
00
0.00
Hz
0.00
Hz
5 - 41
5