Generally, the forward rotation is defined as the direction in which the motor rotates counterclockwise
when viewed from the shaft.
PID Feedback Value Monitor [d004]
Use this function to display the PID feedback value when the PID Selection (A071) is set to 01
(Enabled) or 02 (Reverse output enabled).
The monitor value can be converted by setting the PID Scale (A075) as follows.
d004 = PID Feedback value [%] x PID Scale (A075)
The value of A075 can be set to 0.01 to 99.99 (in increments of 0.01).
Parameter No.
d004
Multi-function Input Monitor [d005]
Use this function to display the input status of each multi-function input terminal, based on whether the
corresponding 7-segment LED is lit or not lit.
The terminal for which the built-in CPU detected the input of a signal is indicated as ON.
Note that this is not affected by the NO/NC contact setting.
(Example)
FW and Multi-function input terminals S7, S2, S1: ON
Multi-function input terminals S8, S6, S5, S4, S3: OFF
ON
FW
(ON)
OFF
Multi-function
input terminals
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Forward
Function name
PID Feedback Value
Monitor
Display
ON
OFF
S8
S7 S6
S5 S4
S3 S2
S1
(OFF) (ON) (OFF) (OFF) (OFF) (OFF) (ON) (ON)
Data
0.00 to 99.99 (Displayed in increments of
0.01)
100.0 to 999.9 (Displayed in increments
of 0.1)
1000. to 9999. (Displayed in increments
of 1)
1000 to 9999 (10000 to 99990)
(Displayed in increments of 10)
Γ100 to Γ999 (100000 to 999000)
(Displayed in increments of 1000,
enabled when the PID function is
selected)
: ON
: OFF