Parameter No.
b101
b103
b105
b107
b109
b111
b113
Related functions
(Example)
Output voltage [V]
Precautions for Correct Use
Precautions for Correct Use
Even if the Free V/f Voltage 1 to 7 are set to 800 V, the inverter cannot produce output voltage
higher than the input voltage or the value of the Motor Rated Voltage Selection (A082).
Be sure to check that the output characteristic setting is proper. An improper setting causes
overcurrent during acceleration or deceleration, or vibration of the motor and/or machine.
Output
voltage [V]
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Function name
Free V/f Voltage 1 (V1)
Free V/f Voltage 2 (V2)
Free V/f Voltage 3 (V3)
Free V/f Voltage 4 (V4)
Free V/f Voltage 5 (V5)
Free V/f Voltage 6 (V6)
Free V/f Voltage 7 (V7)
V7
V6
V5
V4
V1
V2,V3
0
f1
f2
f3
V7
V6
0
f6
Data
Description
Set the voltage
0.0 to 800.0
at each break
point.
A044, A244, A344
Output frequency [Hz]
f4
f5
f6
f7
The output voltage will be limited to the
applicable voltage even if exceeded.
Select the voltage or motor
voltage applicable for output.
f7
Output frequency [Hz]
7 Detailed Functions
Default data
Unit
0.0
V
7 - 37
7