11-1-3 Inspection Items

Inspection
Inspection
category
item
Check ambient
Ambient
temperature,
environment
humidity, and
dust.
General
Check for
Entire
abnormal
system
vibration and
sound.
Power
Check main
supply
circuit voltage.
voltage
Perform megger
check
(between main
circuit terminals
and ground
terminal).
Main
General
circuit
Check for loose
bolts and
screws.
Check each part
for traces of
overheating.
High-function General-purpose Inverter 3G3RX-V1 User's Manual (SBCE-367)
Inspection
frequency
Inspection
Periodic
point
Daily
1
year
11 Maintenance and Inspection
Inspection method
2
years
Refer to 2-1 Installation
on page 2-4.
Perform visual and
acoustic inspection.
Measure line voltage
between Inverter main
circuit terminals R/L1,
S/L2, and T/L3.
Disconnect I/O wires
from the inverter main
circuit terminal block
and remove the control
terminal block PCB.
Then, after removing
the short-circuit bar for
switching the inverter
built-in filter function,
measure using a
megger the resistance
between the ground
terminal and the
short-circuited terminals
R/L1, S/L2, T/L3, U/T1,
V/T2, W/T3, P/+2, +1,
N/–, and RB.
Retighten loose bolts
and screws.
Perform visual
inspection.
Criteria
Meter
Ambient
temperature:
–10 to 50°C,
Thermometer,
no freezing
hygrometer,
Operating
recorder
humidity:
90% max.,
no condensation
No faults
Within allowable
Tester,
AC voltage
digital
fluctuation range
multimeter
500-VDC
5 MΩ min.
class
megger
No faults
No faults