Basic Function Mode; Group F: Basic Function Parameters - Omron RX Series User Manual

High-function general-purpose inverter
Hide thumbs Also See for RX Series:
Table of Contents

Advertisement

4-2

Basic Function Mode

The table below lists the basic function mode parameters.
4-2-1

Group F: Basic Function Parameters

Parameter
Function name
No.
F001
Output Frequency
Setting/Monitor
F002
1st Acceleration
Time 1
F202
2nd Acceleration
Time 1
F302
3rd Acceleration
Time 1
F003
1st Deceleration
Time 1
F203
2nd Deceleration
Time 1
F303
3rd Deceleration
Time 1
F004
RUN Direction
Selection
*1 The default data was changed from the previous model.
Description for Data Range
Data range
0.00 to 99.99
0.0 to 999.9
0. to 9999.
1000 to 9999 (10000 to 99990)
Γ100 to Γ999 (100000 to 999000)
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Monitor or data range
0.0/Starting frequency to
1st/2nd/3rd max. frequency
0.0 to 100.0 (PID function enabled)
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
0.01 to 99.99
100.0 to 999.9
1000. to 3600.
00: Forward
01: Reverse
Description
Displays in increments of 0.01.
Displays in increments of 0.1.
Displays in increments of 1.
Displays in increments of 10.
Displays in increments of 1000.
4 Parameter List
Changes during
Default
operation
data
Normal
b031 = 10
Enabled
Enabled
*1
Enabled
Enabled
10.0
*1
Enabled
Enabled
10.0
Enabled
Enabled
*1
10.0
*1
Enabled
Enabled
10.0
*1
Enabled
Enabled
10.0
*1
Enabled
Enabled
10.0
00
Disabled
Disabled
Unit
Page
Hz
7-14
s
7-15
s
4
s
s
s
s
7-16
4 - 5

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents