5 Basic Settings
Electronic Thermal Characteristics
The electronic thermal function enables you to change the overload detection characteristics by setting
the 1st/2nd/3rd Electronic Thermal Characteristics Selection (b013/b213/b313) according to the motor
in use.
This section first describes the basic electronic thermal characteristics and then provides the details of
individual detection characteristics.
 Basic Characteristics
The electronic thermal characteristics differ between the heavy load mode and the light load mode.
In addition, because the electronic thermal characteristics are different at 75 kW or higher, this
inverter has four basic characteristics as follows.
Basic Characteristics in Heavy Load Mode
Overload detection time [s]
60
3.0
0%
The basic electronic thermal characteristics of four different inverters (Model: 3G3RX-A4750-V1 to
B413K-V1) are as follows.
Basic Characteristics in Heavy Load Mode
Overload detection time [s]
60
3.0
0%
5 - 20
109% 150% 200%
Percentage for rated
output current of
inverter heavy load
Percentage for rated
109% 150% 180%
output current of
inverter heavy load
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Basic Characteristics in Light Load Mode
Overload detection time [s]
60
5.0
109% 120% 150%
0%
Basic Characteristics in Light Load Mode
Overload detection time [s]
60
5.0
0%
109% 120% 150%
Percentage for rated
output current of
inverter light load
Percentage for rated
output current of
inverter light load