Omron RX Series User Manual page 333

High-function general-purpose inverter
Hide thumbs Also See for RX Series:
Table of Contents

Advertisement

Integrated Power Monitor [d015]
Use this function to display the integrated power (integrated input power value) of the inverter.
The monitor value can be converted and displayed with a different scale factor by setting the Integrated
Power Display Scale (b079)
d015 = Calculated input power value [kWh]/Integrated Power Display Scale (b079)
(Example) With the Integrated Power Display Scale (b079) set to 100, the actual integrated power is
100,000 [kWh] when the displayed value is 1,000.
To clear the integrated power value, set the Integrated Power Clear (b078) to 01.
It is also possible to clear the integrated power value via terminal input, if you allocate one of the
Multi-function Input S1 to S8 Selection (C001 to C008) to 53 (KHC: Integrated power clear).
When the Integrated Power Display Scale (b079) is set to 1,000, an integrate power value of up to
999,000,000 [kWh] can be displayed.
Parameter No.
d015
b078
b079
C001 to C008
Total RUN Time Monitor [d016]
Use this function to display the total RUN time of the inverter.
Parameter No.
d016
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Function name
Integrated Power Monitor
Integrated Power Clear
Integrated Power Display
Scale
Multi-function Input S1 to
S8 Selection
Function name
Total RUN Time Monitor
Data
0.0 to 999.9
(Displayed in increments of
1 kWh/(Value set in b079))
1000. to 9999.
(Displayed in increments of 1 kWh/
(Value set in b079))
1000 to 9999 (10000 to 99990)
(Displayed in increments of
1 kWh/(Value set in b079))
Γ100 to Γ999 (100000 to 999000)
(Displayed in increments of
1 kWh/(Value set in b079))
00: Normal
01: Execute Integrated Power Clear.
(Reset from 01 to 00 after
execution.)
1. to 1000.
53: KHC (Integrated power clear)
Data
0. to 9999. (Displayed in increments of
1 hour)
1000 to 9999 (10000 to 99990)
(Displayed in increments of 10 hours)
Γ100 to Γ999 (100000 to 999000)
(Displayed in increments of 1,000 hours)
7 Detailed Functions
Default data
Unit
kWh
00
1.
Default data
Unit
h
7 - 7
7