Using an Analog Voltage Input or Analog Current Input
To use an analog voltage input or analog current input to set the inverter frequency reference, set the
parameters as follows.
This enables the frequency reference input (voltage reference) or frequency reference input (current
directive) terminal.
If inputs are made to both the frequency reference input (voltage reference) and frequency reference
input (current reference) terminals, the sum of the two analog input values will be set as the inverter
frequency reference.
V
• Frequency reference input (Voltage reference), between terminal FV and FC: 0 to 10 VDC
• Frequency reference input (Current reference), between terminal FI and FC: 4 to 20 mA
Note By default, each analog input signal is set to reach the maximum frequency at 9.8 V or 19.8 mA.
Parameter No.
A001
A005
A006
C001 to C008
*1 If C001 to C008 is not set to 16 (AT), FV input and FI input reference values will be added according to the 01
to 03 setting.
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
A
Function name
Frequency
01: Control circuit terminal block
Reference Selection
(Analog input)
00: Switching between FV and FI via
*1
FV/FI Selection
terminal AT
FE Selection
03: FE disabled
Do not set C001 to C008 to 16
Multi-function Input
Terminal
S1 to S8 Selection
(
Data
AT: Analog input switching).
5 Basic Settings
Default
Unit
data
02
00
03
5 - 27
5