5 Basic Settings
Pattern Selection
Select an acceleration/deceleration pattern with reference to the following table.
Parameter
00
No.
Line
A097
(Acceleration)
A098
(Deceleration)
The motor
accelerates/
decelerates linearly
Description
until the set output
frequency value is
reached.
Pattern Curve Parameter (Curve Factor)
Use the following graphs to determine the curve factor.
Output frequency [Hz]
Target
frequency
[100%]
96.9
82.4
17.6
02
3.1
25
Acceleration time until the set
output frequency value [100%]
• The S-shape pattern has a portion where acceleration/deceleration time is faster in the middle of the
curve.
• If the LAD cancel (LAC) function is allocated to a multi-function input terminal and that terminal turns
ON, the acceleration/deceleration pattern is ignored and the output frequency follows the reference
frequency instantaneously.
5 - 38
01
S shape
Time
Time
Time
Time
This pattern is
effective to prevent
the collapse of load
on an elevator,
conveyor, etc.
Output frequency [Hz]
Target
frequency
[100%]
99.6
10
02
93.8
87.5
68.4
64.6
35
10
50
75
Time
High-function General-purpose Inverter 3G3RX-V1 User's Manual (I578-E1)
Set value
02
U shape
Inverted U shape
Time
Time
These patterns are effective for tension
control and roll-break prevention
applications for winding equipment etc.
Target
frequency
[100%]
10
02
10
Time
25
50
75
Acceleration time until the set
output frequency value [100%]
03
04
EL-S shape
Time
Time
Provides shockless
start/stop as with
the S shape, but the
intermediate
section is linear.
Output frequency [Hz]
65
35.4
02
31.6
10
12.5
6.25
0.39
25
50
75
Acceleration time until the set
output frequency value [100%]
Time
Time
Time