Acceleration And Deceleration Characteristics; Setting Acceleration And Deceleration Times - Omron I537-E2-01 User Manual

Table of Contents

Advertisement

Acceleration and Deceleration Characteristics

Setting Acceleration and Deceleration Times

Acceleration time indicates the time to increase the output frequency from 0% to 100% of the maximum out-
put frequency (E1-04). Deceleration time indicates the time to decrease the output frequency from 100% to
0% of (E1-04). The factory setting of the acceleration time is C1-01 and the factory setting of the deceleration
time is C1-02.
Related Parameters
Name
Param-
eter
LCD Display
Number
Acceleration time 1
C1-01
Accel Time 1
Deceleration time 1
C1-02
Decel Time 1
Acceleration time 2
C1-03
Accel Time 2
Deceleration time 2
C1-04
Decel Time 2
Acceleration/deceleration
time switching frequency
C1-11
Acc.Dec SW Freq
S-curve characteristic time at
acceleration start
C2-01
SCrv Acc@Start
S-curve characteristic time at
acceleration end
C2-02
SCrv Dec@ End
Switching Acceleration and Deceleration Time Using Multi-Function Input Terminal Com-
mands
Using the SYSDRIVE PV, you can set two acceleration times and two deceleration times. When the multi-
function input terminals (H1-oo) are set to 7 (acceleration/deceleration time selection 1), you can switch the
acceleration/deceleration time even during operation.
The following table shows the acceleration/deceleration time switching combinations.
Acceleration/Deceleration Time
Selection 1 Terminal
OFF
ON
Description
Set the acceleration time to accelerate from 0 to the maxi-
mum output frequency, in 1-second units.
Set the deceleration time in seconds for the output fre-
quency to fall from 100% to 0%.
Acceleration time when multi-function input "Accelera-
tion/deceleration time selection 1" is ON.
Deceleration time when multi-function input "Accelera-
tion/deceleration time selection 1" is ON.
Set the frequency at which acceleration/deceleration time
switches automatically.
Less than set frequency: Acceleration/deceleration time 2
Set frequency or above: Acceleration/deceleration time 1
Multi-function inputs "Acceleration/deceleration time
selection 1" and "Acceleration/deceleration time selection
2" are given priority.
Set the S-curve characteristic time for each part in sec-
onds.
When you set the S-curve characteristic time, the start time
and end time S-curve characteristic time's acceleration
time is lengthened by 1/2 only.
Run
command
OFF
ON
Output frequency
C2-02
C2-01
The S-curve characteristic time at start and end of deceler-
ation is fixed to 0.2 sec. and can not be changed.
Acceleration Time
C1-01
C1-03

Acceleration and Deceleration Characteristics

Change
Setting
Factory
Range
Setting
Opera-
0.0 to
10.0 s
6000.0
0.0 to
0.0 Hz
120.0
0.00 to
0.20 s
2.50
0.00 to
0.20 s
2.50
Time
Deceleration Time
C1-02
C1-04
during
Access
Level
tion
Yes
Q
Yes
Q
Yes
A
Yes
A
No
A
No
A
No
A
17
6-

Advertisement

Table of Contents

Troubleshooting

loading