Chapter 3. Appendix
15. To configure Shutdown action for the desired events, click on the Shutdown column of the first chosen event.
Green checkmark will be displayed and configuration options will be displayed in the window pane directly below.
Depending on the event, i³ recommends the following settings:
For Battery Capacity 10% or less and for Output Overload events,
a. Check off Enable Shutdown Action checkbox
b. In Operating System Shutdown area,
i. Check off Enable checkbox
ii. Set Delay: time to 2 min, 0 sec
c. In UPS Output Off area,
i. Check off Enable checkbox
ii. Set the Delay: time to 0 min, 0 sec
d. Check off Auto reboot UPS output checkbox
210
Liebert® MultiLink™ Viewer Configuration