RealPresence Collaboration Server (RMX) 1500/1800/2000/4000 Getting Started Guide
Rail Runners Kit Contents
Part/Kit no.
Rail runner assembly kit
Collaboration Server
chassis assembly kit
Telescopic Rail Runner Assembly
Rack Rail Runners require a minimum of 48cm and a maximum of 80cm within the rack for
installation
1 Determine the location of the Collaboration Server on the rack:
Allow for a 1U gap above and below the system for ventilation.
Use the Rack Spacer (item no. 3) to predetermine its position on the rack post, making sure that
square studs of the spacer fit into the rack post's square/rounded mounting holes. Mark the
spacer's location on the rack post. Repeat this process for the 3 remaining vertical posts ensuring
that the system can be horizontally seated.
Polycom®, Inc.
Item
Flat head screw - M3*8mm
Flat washer M3
Nut spring M3
Pan head screw - M5*12mm
Flat washer M5
Item
Item Sample
no.
5
6
7
8
9
Item
Quantity
4
4
4
2
2
34