Using the two wires of a 10 AWG cable running from the DC power distribution unit, connect the black wire into the -48VDC terminal block and the red wire to the RTN terminal block.
A 10 AWG cable must be used to connect the mains with the RealPresence Collaboration Server
(RMX) 4000 DC Power Rail Model.
The supply wires for DC version must be terminated using quick connectors.
Extension cords may not be used.
The center PRM slot/module is fitted with a blank panel and the slot cannot be used on a system
with DC Voltage.
5 Connect the green or green-yellow wire to the system single-point M6x15 "Ground" bolt
.
The rating of the protective earthing conductor should be a minimum of 10AWG.
If the unit is rack mounted, the single-point ground on the MCU must be connected to the rack with a
single conductor and fixed as to prevent loosening. When using bare conductors, they must be
coated with an appropriate antioxidant compound before crimp connections are made. Tinned,
solder-plated or silver plated connectors do not have to be prepared in this manner.
6 Replace the transparent plastic caps on the terminal block.
7 Turn ON the Main that supplies power to the Collaboration Server.