Section 5
DETAILED SETTINGS
Inputting Threshold Values Directly
The threshold values can be set by directly inputting the numeric values.
Direct input is useful when the dimensions for an OK judgement are known beforehand
or when fine-tuning threshold values after teaching.
Moving to T Mode
1.
Set the mode switch to T.
Setting Threshold Values
2.
Move the threshold switch to either H or L,
i.e., the threshold to be set.
The current measured value is shown on the main dis-
play and the threshold being set (value for the threshold
switch selection) will be displayed on the sub-display.
3.
Press one of the Cursor Keys.
The leftmost digit of the threshold value will flash on the
sub-display.
4.
Use the Cursor Keys to set the threshold
value.
5.
Press the ENT Key to confirm the settings.
The threshold values will be registered.
Countermeasures for Setting Errors
One of the following two errors has occurred if the dis-
play reads ERRLH or ERRHL.
HIGH threshold value < LOW threshold value
HIGH threshold value − LOW threshold value < hystere-
sis width
Hysteresis Setting, p. 102
If an error is displayed, the threshold value has not been
updated. Set the threshold values again.
ZX-E
98
Operation Manual
Move between digits.
Increment and decre-
ment the numeric value.