3

Quick Commissioning

3.1

Commissioning with BOP

Motor parameters detailed below are already set for the respective
Siemens motor at the factory. In order to change parameter settings,
use either a BOP/AOP or a Commissioning Tool (e.g., Drive Monitor).
The parameter sequence below ensures optimized and efficient
operation of the inverter. Note that P0010 must be set to 1 to allow this
procedure to be performed.
When fitted, the jumpers override the parameter settings.
P0010
Start Quick
Commissioning
0 = Ready to Run
1 = Quick Commissioning
30 = Factory Setting
Note:
Please note that P0010 must always be
set back to '0' before operating the motor.
However if P3900 = 1 is set after
commissioning this is done automatically.
P0100
Operation for Europe /
N. America
0 =
Power in kW; ƒ default 50 Hz
1 =
Power in hp; ƒ default 60 Hz
2 =
Power in kW; ƒ default 60 Hz
Note:
Settings 0 & 1 can be changed using
Jumper 60 Hz.
P0304
Rated Motor Voltage
10 – 2000 V
Nominal motor voltage (V) from rating plate.
Set in factory for respective motor
P0305
Rated Motor Current
0 – 2 x inverter rated current (A)
Nominal motor current (A) from rating plate.
Set in factory for respective motor.
P0307
Rated Motor Power
0 – 2000 kW
Nominal motor power (kW) from rating
plate. If P0100 = 1, values will be in hp.
Set in factory for respective motor
P0310
Rated Motor Frequency
12 – 650Hz
Nominal motor frequency (Hz) from rating
plate. Set in factory for respective motor.
P0311
Rated Motor Speed
0 – 40000 1/min
Nominal motor speed (rpm) from rating
plate. Set in factory for respective motor
Table Footnotes
1) Denotes parameters that contain detailed lists of possible settings for use in
specific applications. Refer to the Operating Instructions and Operating
Instructions on the CD.
2) Motor related parameters – please refer to motor rating plate drawing.
2)
2)
MICROMASTER 411 & COMBIMASTER 411
Getting Started Guide – 07/05
P0700
0 =
Factory Default
1 =
Basic Operator Panel
2 =
Terminal/Digital Inputs (Default).
P1000
0 =
No frequency setpoint
1 =
BOP frequency control
2=
Analogue Setpoint
27 = Setpoint Addition: Analogue Setpoint
& Control Potentiometer (Default).
2)
P1080
Sets minimum motor frequency (0-650Hz)
at which the motor will run irrespective of
the frequency setpoint. The value set here
is valid for both clockwise and anti-
clockwise rotation.
2)
P1082
Sets maximum motor frequency (0-650Hz)
at which the motor will run at irrespective of
the frequency setpoint. The value set here
is valid for both clockwise and anti-
clockwise rotation.
P1120
0 – 650 s
Time taken for the motor to accelerate from
standstill up to maximum motor frequency.
2)
P1121
0 – 650s
Time taken for motor to decelerate from
maximum motor frequency down to
standstill.
P3900
0 =
No Quick Commissioning without
motor calculation or factory reset.
1 =
Perform Quick Commissioning with
factory reset of all other parameters.
(Recommended)
Selection of Command
1)
Source
(On / off / reverse)
Selection of Frequency
1)
Setpoint
Min. Motor Frequency
Max. Motor Frequency
Ramp-Up Time
Ramp-Down Time
End Quick
Commissioning
1)
15