Technical data
October 2023
Note
For measurements that require a higher measuring accuracy, factory calibrated measuring
chains are available.
Accuracy of measuring chains different from the standard measuring chain
Add the measurement inaccuracies in
accuracy of measuring chains different from the standard measuring chain. The
incremental scale factor (ISF) error is typically ±5%, this applies to 90% of the measuring
range.
Table 11-14: Additional inaccuracies – DSL
Parameter
Other cable lengths
Extended measuring range: 8.0 mm
(Extended range factor: 2.0)
Extended measuring range: 12.0 mm
(Extended range factor: 3.0)
1
Requires previous Automatic calibration, see
sensors
Table 11-15: Sensor temperature inaccuracies – sensor with 4 meters sensor cable
Measuring range
4 mm
11.4.7

AMS EZ 1000 Converter with PR 6426

Typical accuracy of the standard measuring chain following API 670 consisting of PR
6426/0x0-x00 and AMS EZ 1000 Converter with standard target material 42CrMo4 (AISI
4140) and calibration methods Automatic or Multipoint.
118
Automatic calibration
1
Multipoint calibration
Automatic calibration
1
Multipoint calibration
Table 11-14
to the values in
Additional Measurement Inaccuracy
(DSL),
Test range
0.0%
15.0%
2.5%
35.0%
6.0%
Calibration – PR 6424, PR 6425, and PR 6426
Temperature range
-35°C to +85°C
(Operating range converter)
-35°C to +180°C
(Operating range sensor)
-35°C to +380°C
(Operating range sensor)
Operating Manual
MHM-97884
Table 11-13
to get the
Additional linearity error
-8% to +5%
-3% to +5%
-3% to +9%
MHM-97884, Rev. 1.8