10.6

Firmware update

CAUTION
Any work on the system may impair machine protection.
CAUTION
Before starting work on the system, place machine in a safe state and bypass any safety
function that could be affected by the change.
The firmware of the AMS EZ 1000 Converter can be updated by using AMS Machine
Studio.
Note
Emerson recommends saving the configuration of the AMS EZ 1000 Converter before
starting the update process. See operating manual Machine Studio - General Functions
(MHM-97879) for details.
Prerequisites
Ensure that the AMS EZ 1000 Converter to be updated is powered and the following items
are available:
MHM-97884, Rev. 1.8
Figure 10-1: Linearity check
x: Measuring range beginning and end value (-x to 0 to x)
Example: x = 1 mm if an EZ 1080 sensor with a standard measuring range of -1 mm
to +1 mm is used.
The deviation between the ideal distance, described by the
measured distance must be lower than 1%.
Maintenance, fault finding, and repair
Figure
10-1, and the
October 2023
105