Configuration
October 2023
6. Click the measuring button
7. With the micrometer screw, adjust the distance between measuring object and
8. Click the measuring button
84
Figure 8-28: Multipoint calibration
A. Buttons for measurement of converter output voltage.
B. Calibration point for the end of the measuring range (greatest distance between
sensor and measuring object).
C. Calibration point for the center of the measuring range.
D. Calibration point for the beginning of the measuring range (smallest distance
between sensor and measuring object).
E. Indication of the current output voltage of the connected converter.
F. Calibration curve as a result of the calibration points.
Rows C and D are disabled until the measurement for the starting point has been
made (row B).
converter.
This process can take several minutes.
The measured voltage (approximately -18 V) is entered into the related field of
column [V].
sensor tip to the center of the measuring range stated in row C of
converter.
This process can take several minutes.
The measured voltage (approximately -10 V) is entered into the related field of
column [V].
in row B to measure the output voltage of the
in row C to measure the output voltage of the
Operating Manual
MHM-97884
Figure
8-28.
MHM-97884, Rev. 1.8