Step 2 Install the AC output power cable and secure the cable using cable clips.
Figure 10-24 Installing the AC output power cable
----End

10.3.5 Installing an AC Input Power Cable

● A surge protective device (SPD) must be configured for the AC input of the
● Before installing an AC input power cable, ensure that the AC input switch is
● AC switches (with a capacity of 40 A) must be installed for phases L and N of
● No leakage protection device is required for the AC input of the iSitePower-M.
Issue 06 (2023-04-24)
D ANGER
iSitePower-M. You need to configure and install the device by yourself.
turned off and a prominent label indicating "Do not operate" is set.
the iSitePower-M AC input. The AC switches are delivered with the iSitePower-
M. Do not use a Type D circuit breaker because it cannot effectively protect
products.
If a leakage protection device is configured, it is recommended that the leakage
current be greater than or equal to 100 mA x
power modules.
Copyright © Huawei Digital Power Technologies Co., Ltd.
10 Electrical Connections
n , where n is the number of