Page 1
DPU40D-N06A3, DBU20B-N12A3, and DBU50B-N12A1 Distributed Power System User Manual Issue Date 2020-02-29 HUAWEI TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
The "NOTICE", "CAUTION", "WARNING", and "DANGER" statements in this document do not cover all the safety instructions. They are only supplements to the safety instructions. Huawei will not be liable for any consequence caused by the violation of general safety requirements or design, production, and usage safety standards.
1.2 Personnel Requirements Personnel who plan to install or maintain Huawei equipment must receive thorough training, understand all necessary safety precautions, and be able to correctly perform all operations. ...
The power system is designed for wireless base stations and supports online capacity expansion. The DPU40D-N06A3 converts AC or HVDC power into stable 48 V DC power. The lithium battery supplies backup power to communications equipment.
− − Lithium battery: online expansion to increase backup time Easy to maintain Remote monitoring − 2.3 System Configuration Table 2-1 Typical system capacity specifications (DPU40D-N06A3) Number of Number of Number of Power Power Load Routes PSUs (PCS) Lithium...
The PSU needs to support the mobile app function and the connection mode is Bluetooth connection or WiFi connection. Procedure Step 1 Obtain the latest LIVE-C APP installation package from Huawei technical support. Step 2 Install the LIVE-C APP on the mobile phone. Figure 4-1 LIVE-C APP icon ----End 4.2 Logging In to the LIVE-C APP...
Page 34
Huawei will not be liable for any security issues caused by your failure to change the default password in time or password loss after changing. (The password cannot be retrieved if it is lost.) Password Change: System Settings >...
Step 6 Switch on the upstream input circuit breaker for the lithium battery. Step 7 Take off the protective gloves. ----End Follow-up Procedure Pack the faulty component and return it to the local Huawei warehouse. 5.3.3 Replacing a PSU (PSU Only) Prerequisites ...
Step 5 Switch on the upstream input circuit breaker for the PSU. Step 6 Take off the protective gloves. ----End Follow-up Procedure Pack the removed component and return it to the local Huawei warehouse. 5.3.4 Replacing PSUs (Interconnected PSUs) Prerequisites ...
Step 5 Switch on the upstream input circuit breaker for the PSUs. Step 6 Take off the protective gloves. ----End Follow-up Procedure Pack the removed component and return it to the local Huawei warehouse. 5.3.5 Replacing a PSU (PSU Plus Lithium Battery) Prerequisites ...
Step 5 Switch on the upstream input circuit breaker for the PSU. Step 6 Take off the protective gloves. ----End Follow-up Procedure Pack the removed component and return it to the local Huawei warehouse. 5.3.6 Replacing a Lithium Battery (Lithium Battery Only) Prerequisites ...
Use waterproof tape to seal the cable connections. Step 4 Take off the protective gloves. ----End Follow-up Procedure Pack the removed component and return it to the local Huawei warehouse. 5.3.7 Replacing a Lithium Battery (PSU Plus Lithium Battery) Prerequisites ...
Step 5 Switch on the upstream input circuit breaker for the PSU. Step 6 Take off the protective gloves. ----End Follow-up Procedure Pack the removed component and return it to the local Huawei warehouse. 5.3.8 Replacing a DC Fuse Prerequisites ...
5%-95% RH (non-condensing) humidity Storage humidity 5%-95% RH (non-condensing) DPU40D-N06A3, DBU20B-N12A3 and DBU50B-N12A1: –60 m to Altitude 4000 m (When the altitude ranges from 2000 m to 4000 m, high temperature derating applies and the operating temperature decreases by 1° C for each additional 200 m.) Class C environments refer to sea environments or outdoor land environments (with simple shielding measures) near pollution sources.
Page 65
MTBF electrochemical cell) Dimensions (H x W 420 mm x 120 mm x 300 mm x D) ≈ 26 kg Weight Table A-5 DPU40D-N06A3 EMC specifications Item Specifications Electromagnetic Conducted emission Input: Class B, EN55032 (AC input)/Class A interference (EMI)