iSitePower-M (MAP05A1, MAB05B1)
User Manual
Table 5-2 Terminals on the panel
Pin
1
2
3
4
5
6
7
9
10
8
Note [1]: For a genset that starts when the dry contact is open, connect the
signal cable to ports NC and COM. For a genset that starts when the dry contact
is closed, connect the signal cable to ports NO and COM.
WiFi Switch
The power module has a built-in WiFi module. You can press the WiFi switch to
enable or disable WiFi and reset the WiFi password and user login password.
Issue 06 (2023-04-24)
Signal
-
NC
COM
NO
DIN1+
DIN1–
DIN2+
DIN2–
GND
Enable/Disable WiFi: Hold down the WiFi switch for at least 10s to enable or
disable WiFi. The WiFi function is disabled by default.
Reset the WiFi password and user login password: Press the WiFi switch for
three times within 10s and each time lasts for 1s. Wait for more than 1s each
time before pressing the switch again. Then the WiFi module is restarted, and
the WiFi password and user login password are reset successfully.
The last six digits of the product WiFi name are the same as the last six digits
of the product SN. The default password is Changeme.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
-
Dry contact output
normally closed
(NC) terminal
Dry contact output
common terminal
Dry contact output
normally open
(NO) terminal
Dry contact input
DIN 1
Dry contact input
DIN 2
-
5 Components
Function
Reserved ports
Connect to a genset
and control genset
startup and shutdown
[1]
signals
.
● Connect to an ATS.
In the mains+genset
scenario, the DIN
dry contacts are
used to detect
mains signals.
● Connect to an EPO
switch to remotely
shut down the
equipment.
-
41