Huawei iSitePower-M MAP05A1 User Manual page 99

Hide thumbs Also See for iSitePower-M MAP05A1:
Table of Contents

Advertisement

iSitePower-M (MAP05A1, MAB05B1)
User Manual
No.
One End
3
Ground
point
4
Ground
point
Table 9-6 Cables in parallel-system scenarios
No.
One End
1
Ground
point
2
AC parallel
box
3
AC parallel
box
4
AC parallel
box
5
AC parallel
box
6
AC parallel
box
Issue 06 (2023-04-24)
Other End
Type
Site ground
Outdoor single-core
bar
copper cable
(customer
side)
Ground point
Outdoor single-core
on the
copper cable (capacity
module for
expansion scenario)
capacity
expansion
Other End
Type
Site ground
Outdoor single-core
bar
copper cable
(customer
side)
AC PDC
Outdoor three-core copper
(customer
cable (L/N/PE)
side)
AC output
Outdoor three-core copper
port
cable (L/N/PE)
AC input port
Outdoor three-core copper
cable (L/N/PE)
PDB
Outdoor three-core copper
(customer
cable (L/N/PE)
side)
Site ground
Outdoor single-core
bar
copper cable
(customer
side)
Copyright © Huawei Digital Power Technologies Co., Ltd.
9 Preparing Cables
Recommended
Specifications
Conductor cross-sectional
2
area: 4–6 mm
(same as
the cross-sectional area of
the AC input power cable)
Conductor cross-sectional
2
area: 6 mm
Recommended
Specifications
Main PE cable: 4–6 mm
(same as the cross-sectional
area of the AC input power
cable)
● Conductor cross-
sectional area: 25 mm
● Cable outer diameter:
16–26 mm
● Conductor cross-
sectional area: 4–6 mm
● Cable outer diameter:
13.7–16.9 mm
● Conductor cross-
sectional area: 4–6 mm
● Cable outer diameter:
13.7–16.9 mm
● Conductor cross-
sectional area: 25 mm
● Cable outer diameter:
16–26 mm
● Conductor cross-
sectional area: 25 mm
● Cable outer diameter: 8–
11 mm
2
2
2
2
2
2
90

Advertisement

Table of Contents
loading

This manual is also suitable for: