5 PROTECTION

5.1 WARNING ALARM

When controller detects the warning alarms, it only issues alarm and does not stop the genset. Alarm
is not issued until the alarm is enabled and the action type is selected
No.
1
Busbar Over Voltage
2
Busbar Under Voltage
3
Busbar Over Frequency
4
Busbar Under Frequency
5
Busbar Reverse Power
6
Busbar Over Power
7
Busbar Reverse Phase
8
Busbar Loss of Phase
9
Busbar Unbalanced Voltage
10
PV Over Voltage 1
11
PV Under Voltage 1
12
PV Over Frequency 1
13
PV Under Frequency 1
HES7120-PV Hybrid Engergy Controller
HES7120-PV HYBRID ENERGY CONTROLLER USER MANUAL
Table 7 Warning Alarm Types
Type
Description
When the controller detects the corresponding data
value ≥ (overvoltage, overfrequency alarm, etc.) or ≤
(undervoltage, under frequency alarm, etc.) the
threshold value, the alarm is enabled and the action
type is selected, the controller will send out a
warning signal.
When the controller detects that the absolute value
of busbar power value (power is negative) ≥ the set
threshold value, the alarm is enabled and the action
type is selected to warn, the controller will send out a
warning signal.
When the controller detects that the power value of
the busbar (power is positive)≥ the set threshold
value, the alarm is enabled and the action type is
selected, the controller will send out a warning
signal.
When the controller detects the loss of busbar
phase, the controller will send out a warning signal
when the alarm is enabled.
When the controller detects the reverse phase
sequence of the busbar and the alarm is enabled,
the controller sends out a warning signal.
When the controller detects that the voltage
unbalance percentage of the busbar ≥ the set
threshold value, and the alarm is enabled and the
action type is selected, the controller will send out a
warning signal.
When the controller detects the corresponding data
value ≥ (overvoltage, overfrequency alarm, etc.) or ≤
(undervoltage, under frequency alarm, etc.) the
threshold value, the alarm is enabled and the action
type is selected, the controller will send out a
warning signal.