Synchronize The Control Units (H8/S8) - Panasonic MEW01349 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01349
31.9
Action
"Menu"
"↵ "
Scroll to menu S8.
"↲ "
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x

Synchronize the control units (H8/S8)

After any control unit restart, synchronization will start automatically.
Synchronization can also be started via WinG3 and via this menu
(H8/S8).
The control units have to be synchronized when the following fault
message is shown:
During the synchronization there will be information displayed for all
control units in the system.
↻ (rotating clockwise) = Synchronization in progress for the
control unit (CU).
 = Synchronization completed successfully for the control unit
(CU).
<Blank> = Synchronization failed for the control unit (CU).
Text in display
S1 Disconnect loop / zone line input
S2 Re-connect loop / zone line input
S3 Acknowledge SERVICE signal
S4 Clear weekly average
S5 Test of alarm devices
S6 Safe shut down of control unit
S7 Activate address in alarm mode
S8 Synchronize the control units
S9 Change code for service / maintenance
S10 Change code for PC-communication
S8 Synchronize the control units
Start synchronization?
FAULT: Control unit xx has wrong information.
No
Yes
141
Comments
Procedure according to
chapter "Access code for
service / maintenance (H5
and H8)", see page 116.
Press "▼", i.e. select
"↲ "
"Yes". Press
to start
the synchronization.