Sensitive Fault Detection Mode (H5/A4) - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
28.4
Action
"Access"
Scroll to menu A4
"A"
E.g. "1", "A"
Rev: 3
NOTE!
After the calibration it is recommended to do a "Safe
shutdown of control unit" (see menu H8/S4). This will save the SSW
data (e.g. the calibration values) in a Flash ROM (see page 74).

Sensitive fault detection mode (H5/A4)

"Sensitive fault detection mode" means that the time delay is reduced
for all type of faults, which makes it possible find faults during the
commissioning instead of later.
NOTE! Don't forget to turn this mode off after the commissioning.
Text in display
Disconnect / Re-connect COM loop
Sensitive fault detection mode
Sensitive fault detection mode: 0
(0 = off, 1 = on)
Sensitive fault detection mode
NOTE! Don't forget to turn this mode off after the commissioning.
EBL128 Operating Instructions V1.1.x
ACCEPT? A1
ACCEPT? A4
ACCEPT? A4
108
Comments
According to chapter
"Access code for service
and maintenance", see
page 104.
Press "A" or "1" and "A"
to accept. ON is indicated
by LED "Fault tx
activated" (L11) and the
"Fault" output for routing
equipment. This mode is
ON until turned OFF in
this menu (A4).
Scroll or press "Return" to
H5. Scroll or press
"Return" to log off.