Perform Monthly Test (H1) - Panasonic MEW01777 Operating Instructions Manual

Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01777
23
Action
"
"
Menu
"
"
"
"
"
"
Write zone numbers
(e.g. 001, 002, 003,
004)
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V2.2.x

Perform monthly test (H1)

The control unit and the installation shall be tested on a regular basis.
If one twelfth of the alarm points are tested each month, the whole
installation will be tested after one year.
In test mode, only the alarm points are tested, i.e. no outputs (no
sounders) will be activated during the test. (Alarm devices can be
tested via menu H8/S4.)
If a real fire alarm is activated, for example by an alarm point not in
test mode, the normal fire alarm functions will be activated, i.e. fire
alarm presentation, outputs (sounders) activated, routing equipment
(fire brigade tx) activated, etc.
See also chapter "The information area priority order", page 24.
NOTE! If the control unit door is left open, the output(s) for routing
equipment (fire brigade tx) might be disabled (if set so in EBLWin).
See also chapter "Perform ZONE TEST (Test mode) (H7)", page 134.
Text in display
H1 Perform monthly test
Check that all LEDs light up!
Press 
[ A l l d o t s a r e v i s i b l e ]
Zones to be set in test mode:
??? ??? ??? ??? Start test: 
Zones to be set in test mode
001 002 003 004
91
Comments
According to chapter
Access
"
", see page 88.
The buzzer (in the C.U.)
sounds and all dots in the
display are shown. All
LEDs light up, incl. LEDs
in units connected via I/O
Matrix board 4582.
If a printer is mounted in
the c.i.e. it will print out:
ABCDE............Z
abcde............z
Press "
" to start the test
mode.