Perform monthly test (H1)

Not available for users with access level / type "Information only".
Regarding the "Test mode" (see
Log in with a User name and Password for typ Building officer (or
Service personnel), see page 5.
H1 Perform monthly test
Press "A".
Check that all LEDs light up!
Press "A".
The c.i.e. buzzer sounds, all the dots in the display are shown and all
LEDs on the front are turned on.
Press "A". Up to four zones can be set in test mode. Use the keypad
to type the zone numbers. Press "A" to start the test.
Perform the tests. Press "A" to end the test..
If the routing equipment shall not be tested press "A" and the
monthly test is completed. Press "A" to menu H1. Go to
If the routing equipment shall be tested press "1". To start the test
press "A". Started test is indicated by LED "Fault tx activated" (L11)
and after 30 seconds also LED "Fire brigade tx" (L5).
seconds (in total) the routing equipment test is ended and the LEDs
are turned off. The monthly test is completed. Press "A" to menu H1.
Menu H1 is shown. Scroll to another menu or leave the menu system
by pressing "Return" (P9).
4
If a "Fire brigade tx" output is programmed.
EBL128 version 2.0.x, Daily user's manual