11
Low Coolant Level
12
Temp. Sensor Open
Oil Pressure Sensor
13
Open
14
Level Sensor Open
15
Temp. Sensor 2 Open
Oil Pressure Sensor 2
16
Open
17
Coolant Level 2 Open
High
18
Temperature 2
19
Low Oil Pressure 2
20
Coolant Level 2
21
Maintenance Due
HGM410DC Genset Controller
When the controller detects the low coolant level input is active, it will
initiate a warning alarm and the corresponding alarm information will be
displayed on LCD.
When the controller detects that the temperature sensor is open circuit and
the action select "Warn", it will initiate a warning alarm and the
corresponding alarm information will be displayed on LCD.
When the controller detects that the oil pressure sensor is open circuit and
the action select "Warn", it will initiate a warning alarm and the
corresponding alarm information will be displayed on LCD.
When the controller detects that the level sensor is open circuit and the
action select "Warn", it will initiate a warning alarm and the corresponding
alarm information will be displayed on LCD.
If the config. sensor set as temperature sensor, When the controller
detects that the temperature sensor is open circuit and the action select
"Warn", it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD.
If the config. sensor set as oil pressure sensor, When the controller detects
that the oil pressure sensor is open circuit and the action select "Warn", it
will initiate a warning alarm and the corresponding alarm information will
be displayed on LCD.
If the config. sensor set as level sensor, When the controller detects that
the level sensor is open circuit and the action select "Warn", it will initiate a
warning alarm and the corresponding alarm information will be displayed
on LCD.
When the controller detects that config. sensor temperature (sensor type:
temperature sensor) has exceeded the pre-set value while shutdown is
prohibited, it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that config. sensor oil pressure (sensor type:
oil pressure sensor) has fallen below the pre-set value while shutdown is
prohibited, it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD.
When the controller detects that config. sensor fuel level (sensor type:
level sensor) has fallen below the pre-set value while shutdown is
prohibited, it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD.
When the genset running time has exceeded the pre-set maintenance
time, it will initiate a warning alarm and the corresponding alarm
information will be displayed on LCD. When the maintenance is inactive,
the alarm resets.
2015-11-12
HGM410DC Genset Controller User Manual