4.2

PANEL

4.3

AUTOMATIC START/STOP OPERATION

Auto mode is selected by pressing the
the operation.

4.3.1 Auto Remote Start Sequence

HGM410DC: When "Remote Start" is active, "Start Delay" timer is initiated;
1)
"Start Delay" countdown will be displayed on LCD;
2)
When start delay is over, preheat relay energizes (if configured), "preheat delay XXs" information
3)
will be displayed on LCD;
4)
After the above delay, the Fuel Relay is energized, and then one second later, the Start Relay is
engaged. The engine is cranked for a pre-set time. If the engine fails to fire during this cranking
attempt then the fuel relay and start relay are disengaged for the pre-set rest period; "crank rest
time" begins and wait for the next crank attempt.
5)
Should this start sequence continue beyond the set number of attempts, the start sequence will be
terminated, the fourth line of LCD display will be highlighted with black and Fail to Start fault will be
displayed.
In case of successful crank attempt, the "Safety On" timer is activated, allowing Low Oil Pressure,
6)
High Temperature, Under speed, Charge Alternator Failure and Auxiliary inputs (configured) to
stabilise without triggering the fault. As soon as this delay is over, "start idle" delay is initiated (if
configured).
During "start idle" delay, under speed, under frequency, under voltage alarms are inhibited. When
7)
this delay is over, "warming up" delay is initiated (if configured).
After the "warming up" delay, if generator status is normal, its indicator will be illuminated. If
8)
generator voltage and frequency have reached on-load requirements, then the generator close
HGM410DC Genset Controller
HGM410DC Genset Controller User Manual
button; a LED besides the button will illuminate to confirm
2015-11-12
Version 1.0
Page 8 of 34