Smartgen HGM410DC User Manual page 21

Genset controller
Table of Contents

Advertisement

No
Items
85.
Gen Over Freq Warn
86.
Gen Under Freq Warn
Over
87.
Percentage
88.
High Temperature
89.
Low Oil Pressure
90.
Over Volt Delay
91.
Over Freq Delay
Bat Under Volt Start
92.
Enabled
Bat Under Volt Start
93.
Threshold
Bat Under Volt Start
94.
Delay
HGM410DC Genset Controller
Range
(0-75.0)Hz
(0-75.0)Hz
Current
(0-130)%
(80-140)℃
(0-400)kPa
(0-20.0)s
(0-20.0)s
(0-1)
(0-60.0)V
(0-500)min
2015-11-12
HGM410DC Genset Controller User Manual
Default
Description
When generator frequency has exceeded
55.0
the set value, Over Frequency is active. It
will initiate a warn signal.
When generator frequency has fallen below
47.0
the set value, Under Frequency is active. It
will initiate a warn signal.
When load current has exceeded the set
value, Over Current is active. It will not
110
initiate a warn signal when set this value as
0.
When the temperature value of the external
temperature sensor exceeds the set value,
"High
Temperature"
Detecting only after safety on delay has
95
expired. If the set value is 140, high
temperature signal will not be sent (this only
concerns external temperature sensor, not
high temperature signal via configurable
input port).
When the external pressure sensor value
falls below this set value, "Low Oil Pressure"
timer is initiated. Detecting only after safety
on delay has expired. If the set value is 0,
124
low oil pressure signal will not be sent (this
only concerns pressure sensor and does not
concern low oil pressure warning signal via
configurable input port)
When generator voltage has exceeded
10.0
shutdown threshold value and last for this
delay time, Over Volt Shutdown is active.
When generator frequency has exceeded
10.0
shutdown threshold value and last for this
delay time, Over Freq Shutdown is active.
0: Disabled; 1: Enabled
1
Battery under voltage start is enabled.
When the battery voltage falls below battery
8.0
under volt start threshold and last for 2s,
Battery Volt Abnormal signal is sent. This
value only warns but not shutdown. When
the controller is in auto mode, it hints Bat
5
Under Volt Start Delay. When battery under
volt last until that delay ends, the genset will
start automatically.
Version 1.0