Smartgen HGM410DC User Manual page 20

Genset controller
Table of Contents

Advertisement

No
Items
Multiplex Aux. Sensor
70.
Input
71.
Config. Sensor Curve
72.
Poles
Temperature
73.
Open
Oil
Pressure
74.
Open
75.
Fuel Level Sensor Open
76.
Config. Sensor Open
77.
Air-cooler On Temp.
78.
Air-cooler Off Temp.
79.
Low Fuel Level Warn
80.
Maintenance Enabled
81.
Maintenance Time
82.
Maintenance Due
83.
Gen Over Volt Warn
84.
Gen Under Volt Warn
HGM410DC Genset Controller
Range
(0-3)
(0-9)
(0-9)
(0-5)
(2-32)
Sensor
(0-2)
Sensor
(0-2)
(0-2)
(0-2)
(0-140)℃
(0-140)℃
(0-100)%
(0-1)
(0-5000)h
(0-1)
(30-620)V
(30-620)V
2015-11-12
HGM410DC Genset Controller User Manual
Default
Description
0: Aux. Input 4
1: Temperature Sensor
0
2: Oil Pressure Sensor
3: Level Sensor 7.1 Note 3
8
SGX
8
SGX
3
SGD
4
0: Indication (temperature sensor will show
"+++");
1
1:Warn; 2:Shutdown
0: Indication (oil pressure sensor will show
"+++");
1
1:Warn; 2:Shutdown
0: Indication (fuel level sensor will show
"+++");
1
1:Warn; 2:Shutdown
0: Indication (LCD display will show "+++");
1
1:Warn; 2:Shutdown
60
When an output port was set to air-cooler
output, it will control the air-cooler to
40
start/stop.
When the liquid level of the external sensor
falls below the set value, "Low Fuel Level"
timer is initiated. (this only concerns fuel
20
level sensor and does not concern low fuel
level warning signal via configurable input
port)
0: Disabled
0
1: Enabled
30
Used to set maintenance rest time.
0
0:Warn;1:Shutdown
When generator voltage has exceeded the
set value and the "Gen Over Volt delay" has
240
expired, Gen Over Voltage is active. When
set the value as 620V, the controller does
not detect over voltage signal.
When generator voltage has fallen below the
set value and the "Gen abnormal delay" has
210
expired, Gen Under Voltage is active. When
set the value as 30V, the controller does not
detect under voltage signal.
Version 1.0
Page 21 of 34