7.2 PROGRAMMABLE OUTPUT 1-5

No
Items
0
Not Used
1
Common Alarm
2
Energized to Stop
3
Idle Control
4
Preheat Control
5
Close Generator
6
Reserved
7
Open ATS
8
Raise Speed
9
Drop Speed
10
Generator Run
11
Fuel Pump Control
12
High Speed Control
13
In Auto Mode
14
Fuel Relay Output
15
Generator Excite
16
Air-cooler
17
Louver Control
HGM410DC Genset Controller
Output port is deactivated when "Not Used" is selected.
Include all shutdown alarms and warning alarms. When there is
warning alarm only, it is not self-lock; when a shutdown alarm occurs, it
is self-lock until the alarm is reset.
Suitable for genset with electromagnet and will active after "stop idle
delay". It is deactivated when the "ETS Solenoid delay" expires.
Used for engine which has idles. Close before starting and open in
warming up delay; Close during stop idle delay and open when stop is
completed.
Close before starting and open before power up;
When close time is 0, it's continuous output.
When close time is 0, it's disabled.
Close when the generator enters into Warming Up delay (close time:
warming up delay) while open when Aux.
Close when the generator enters into Stop Idle delay/ Energized to Stop
delay (close time: Stop Idle delay) while open when Aux.
Action when genset is normal running while deactivated when engine
speed is lower than the "crank disconnect speed".
Close when fuel level is lower than the "Fuel Pump On" value or when
low fuel level warning input is active; Open when fuel level is higher
than the "Fuel Pump Off" and low fuel level warning input is deactivated;
Close when the generator enters into Warming Up delay while open
after cooling delay.
The controller is in automatic mode.
To control fuel relay output.
Output in start period. If there is no generator frequency during safety
running, output for 2 seconds.
Control air-cooler to start/stop according to air-cooler switch
temperature.
Active when gens starting, open after gens stop.