No
Items
49.
Aux. Input 3 Active
50.
Aux. Input 3 Delay
51.
Aux. Input 4
52.
Aux. Input 4 Active
53.
Aux. Input 4 Delay
54.
Power On Mode
55.
Module Address
56.
Passwords
57.
Crank Disconnect
Disconnect
58.
Pickup
Disconnect
59.
Freq
60.
Disconnect Oil Pressure
61.
High Temperature Inhibit (0-1)
62.
Low Oil Pressure Inhibit
63.
Low Fuel Level Inhibit
64.
Config. Sensor Inhibit
65.
AC System
66.
Temp. Sensor Curve
67.
Pressure Sensor Curve
Multiplex Level Sensor
68.
Input
69.
Level Sensor Curve
HGM410DC Genset Controller
Range
(0-1)
(0-20.0)s
(0-31)
(0-1)
(0-20.0)s
(0-1)
(1-254)
(0-9999)
(0-5)
Magnetic
(0-3000)r/min 360
Generator
(10.0-30.0)Hz 14.0
(0-400)kPa
(0-1)
(0-1)
(0-1)
(0-3)
(0-9)
(0-9)
(0-2)
(0-5)
HGM410DC Genset Controller User Manual
Default
Description
0
Factory default: Close to active
2.0
11
Factory default: Fuel Level Warn
0
Factory default: Close to active
2.0
0: Stop Mode
0
1: Auto Mode
1
Communication address of controller.
1234
There are 3 conditions of disconnecting
starter with engine: Generator Frequency,
Magnetic
2
condition
simultaneously to separating the start motor
and genset as soon as possible.
See 7.5
When engine speed higher than the set
value, starter will be disconnected.
When generator frequency higher than the
set value, starter will be disconnected.
When generator oil pressure higher than the
200
set value, starter will be disconnected.
Factory default: when high temperature
0
occurs, shutdown alarm is initiated. 7.1Note
1
Factory default: when low oil pressure
0
occurs, shutdown alarm is initiated. 7.1 Note
2
Factory default: when low fuel level occurs,
1
shutdown alarm is initiated.7.1 Note 2
Factory default: when config. sensor value
higher/lower than the set value (particular
1
case depends on the sensor type), shutdown
alarm is initiated.
7.1 Note 2
0: 3P4W; 1: 2P3W
0
2: 1P2W; 3: 3P3W 7.1 Note3
08
SGX
08
SGX
0: Aux. Input 3
0
1: Level Sensor
7.1 Note 3
3
SGD
2015-11-12
Pickup,
Oil
Pressure.
can
be
used
Version 1.0
Each
alone
and
Page 20 of 34