Smartgen HGM410DC User Manual page 22

Genset controller
Table of Contents

Advertisement

No
Items
Bat
Normal
95.
Threshold
96.
Bat Normal Shut Delay
97.
Self-check Delay
98.
Self-check Time
99.
Custom Sensor Curve
Note 1: if "high temperature inhibit" is configured, or set auxiliary input as "inhibit high temperature
stop" and this input is active, when temperature is higher than the preset value, or high temperature alarm
input is active, controller will send warning signal only and not stop the unit.
Note 2: if "low oil pressure inhibit" is configured, or set auxiliary input as "inhibit low oil pressure stop"
and this input is active, when oil pressure is lower than the preset value, or low oil pressure alarm input is
active, controller will send warning signal only and not stop the unit.
Note 2: if "3-phase 3-wire" is configured, the maximum of generate over voltage shutdown threshold
can be set to 620V; if it is not configured, then the maximum only can be set to 360V;
Note 4: Multiplex Input can be set as "auxiliary input" or "level sensor"; if one of them is set
successfully, then the corresponding items are active. For instance, if set "Multiplex Input 3" as "Aux.
Input", the related configuration items of auxiliary input 3 are active; if set "Multiplex Input 3" as "Level
Sensor", the related configuration items of level sensor are active.
HGM410DC Genset Controller
Range
Shut
(0-60.0)V
(0-500)min
(0-9999)h
(0-500)min
(0-3)
2015-11-12
HGM410DC Genset Controller User Manual
Default
Description
If the battery is in auto mode due to battery
13.0
under volt start, the controller hints Battery
Normal Shut Delay when battery voltage has
exceeded normal shutdown threshold; when
5
battery is normal until the delay ends, genset
will stop.
Begin to time from last shutdown. When the
accumulated time has exceeded or equal to
336
self-check delay and the controller is in auto
mode, the genset will start to run; when the
accumulated time has exceeded or equal to
self-check time, the genset stops. When the
30
self-check delay is set to 0, the function is
deactive.
It can be customized as Temp. Sensor, OP
0
sensor, Level Sensor or Config. Sensor
curve.