Auto Remote Stop Sequence; Battery Under Volt Start/Stop Sequence; Auto Self-Check Start Sepuence; Manual Start/Stop Operation - Smartgen HGM410DC User Manual

Genset controller
Table of Contents

Advertisement

relay will be energized; genset will take load; generator power indicator will illuminate and
generator will enter into Normal Running status. If voltage or frequency is abnormal, the controller
will initiate shutdown alarm (alarm information will be displayed on LCD).

4.3.2 Auto Remote Stop Sequence

When the "Remote Start" signal is removed, the Stop Delay is initiated.
1)
Once this "stop delay" has expired, the Generator Breaker will open, the "Cooling Delay" is then
2)
initiated and generator power indicator will extinguish.
During "Stop Idle" Delay (if configured), idle relay is energized.
3)
"ETS Solenoid Hold" begins, ETS relay is energized while fuel relay is de-energized.
4)
5)
"Fail to Stop Delay" begins, complete stop is detected automatically.
6)
Generator is placed into its standby mode after its complete stop. Otherwise, fail to stop alarm is
initiated and the corresponding alarm information is displayed on LCD.

4.3.3 Battery Under Volt Start/Stop Sequence

1)
HGM410DC battery under voltage function is enabled;
2)
When battery voltage under than battery under voltage threshold is detected, Battery Under Volt is
displayed on LCD after 2s and the Under Volt Start Delay is initiated;
3)
Battery Under Volt Start Delay is displayed on LCD;
4)
Same with Step 3)~8) of Auto Remote Start Sequence after delay;
5)
When battery voltage over than battery normal stop threshold is detected, Battery Normal Stop
Delay is initiated;
6)
Battery Normal Stop Delay count down is displayed on LCD;
7)
Same with Step 2)~6) of Auto Remote Stop Sequence after delay.

4.3.4 Auto Self-check Start Sepuence

1)
When self-check delay of HGM410DC is larger than 0, genset self-check is enabled;
2)
The genset start time from last stop and Self-check Count Down is initiated;
3)
Self-check Count Down is displayed on LCD;
4)
Same with Step 3)~8) of Auto Remote Start Sequence;
5)
Self-check Working is initiated after genset start;
6)
Self-check Working is displayed on LCD;
7)
Same with Step 2)~6) of Auto Remote Stop Sequence after delay.

4.3.5 Manual Start/Stop Operation

1)
Press
key to enter into Manual Mode and the Manual Indicator will illuminate. Then press
key to start the generator, it can automatically judge crank success and accelerate to high speed
running. If high temperature, low oil pressure, over speed and abnormal voltage occur during
genset running, controller can effectively protect genset to stop (detail procedures please refer
to No.4.3.1 5)~8) of Auto start sequence). After genset high speed normal running, controller will
send Gen Closed signal.
2)
Manual stop: pressing
4.3.2 1)~6) of Auto stop sequence)
HGM410DC Genset Controller
key can stop the running genset. (Details procedures please refer to No.
2015-11-12
HGM410DC Genset Controller User Manual
Version 1.0
Page 9 of 34