Definition And Range Of Parameters; Parameter Contents And Range - Smartgen HGM410DC User Manual

Genset controller
Table of Contents

Advertisement

7

DEFINITION AND RANGE OF PARAMETERS

7.1 PARAMETER CONTENTS AND RANGE

No
Items
1.
Start Delay
2.
Stop Delay
3.
Start Attempts
4.
Preheat Time
5.
Cranking Time
6.
Crank Rest Time
7.
Safety On Delay
8.
Start Idle Time
9.
Warming Up Time
10.
Cooling Time
11.
Stop Idle
12.
ETS Solenoid Hold
13.
Fail to Stop Delay
14.
Breaker Close Time
15.
Flywheel Teeth
16.
Gen Abnormal Delay
17.
Gen Over Voltage
HGM410DC Genset Controller
Range
Default
(0-3600)s
1
(0-3600)s
1
(1-10)times
3
(0-300)s
0
(3-60)s
8
(3-60)s
10
(1-60)s
10
(0-3600)s
0
(0-3600)s
10
(3-3600)s
10
(0-3600)s
0
(0-120)s
20
(0-120)s
0
(0-10)s
5.0
(10-300)
118
(0-20.0)s
10.0
(30-620)V
264
2015-11-12
HGM410DC Genset Controller User Manual
Description
Time from mains abnormal or remote start
signal is active to start genset.
Time from mains normal or remote start
signal is deactivated to genset stop.
Maximum crank times of crank attempts.
When reach this number, controller will send
start failure signal.
Power-on time of heater plug before starter
is powered up.
Power-on time of starter
The waiting time before second power up
when engine start fail.
Alarms
for
low
temperature,
under
frequency/voltage, charge alt failure are
inactive.
Idle running time of genset when starting.
Warming time between genset switch on and
high speed running.
Radiating time before genset stop, after it
unloads.
Idle running time when genset stop.
Stop electromagnet's power on time when
genset is stopping.
Time between ending of genset idle delay
and stopped when "ETS time" is set as 0;
Time between ending of ETS hold delay and
stopped when "ETS time" is not 0.
Pulse width of mains/generator switch on.
When it is 0, means output constantly.
Tooth number of the engine, for judging of
starter crank disconnects conditions and
inspecting of engine speed. See the
installation instructions.
The alarm delay of generator over voltage
and under voltage.
When generator voltage has exceeded the
set value and the "Gen abnormal delay" has
expired, Gen Over Voltage is active. When
set the value as 620V, the controller does
not detect over voltage signal.