9.16

Synchronous Output Timing Setting Function

This function sets the output timing of the main output module that operates synchronously using CC-Link IE Field
Network synchronous communication function. The ON/OFF of output signal is changed at any timing, regardless of
the synchronization cycle, using the function.
Synchronization cycle of the master station
Scan program
Synchronization
control interrupt
program
External output Y
(a status of the Yn
terminal) of the output
module
The synchronous output timing setting function uses the following devices.
• "Synchronous output timing setting Y0 OFF to ON" to "Synchronous output timing setting YF ON to OFF"
(RWw14 to RWw33) ( Page 268, Appendix 2 (13))
• Synchronous output timing setting function enable (address: 0104H) ( Page 272, Appendix 3 (7))
• Only the NZ2GF2B1N-16T, NZ2GF2B1N-16TE, NZ2GF2S1-16T, and NZ2GF2S1-16TE can use the synchronous
output timing setting function.
• External output signals (RY0 to RYF) of the output module using the synchronous output timing setting function
becomes disabled.
• The CC-Link IE Field Network synchronous communication function is required to use the synchronous output
timing setting function. ( Page 198, Section 9.13)
• The synchronous output timing setting function is enabled when the NZ2GF2B1N-16T, NZ2GF2B1N-16TE,
NZ2GF2S1-16T, or NZ2GF2S1-16TE operates in synchronous communication mode.
• When External output Y is output to a connected device, the device recognizes the output with delay of
maximum output response time. Therefore, if the ON/OFF switching period of output is set to be shorter than
maximum output response time, the connected device may not turn on or off.
206
(3ms)
Operation
1)
Synchronous output timing setting Y
Synchronous output timing setting Y
Operation
Synchronous output timing setting Y
Synchronous output timing setting Y
2)
OFF to ON: 105 (10.5μs)
ON
ON to OFF: 50000 (5000.0μs)
Turns on after 10.5μs.
Operation
OFF to ON: 105 (10.5μs)
ON to OFF: 200 (20.0μs)
The output does not turn off because the set value
in Synchronous output timing setting Y
longer than the synchronization cycle of the master station.
Turns off after
20.0μs.
ON to OFF is